Sizing a 24 V battery for control-panel backup

A small DC load is turned into a 24 V battery size. The inputs are assumptions for illustration.

Illustrative worked example. The inputs are assumptions, not a customer project. The arithmetic is real.

The scenario

A process plant needs to keep a 24 V control panel running during outages. The load is 10 A and the target is 8 hours.

Energy needed

24 V × 10 A = 240 W. Over 8 hours that is 1,920 Wh, or 1.92 kWh. If 90% of the battery is usable, the nominal energy is about 2.13 kWh.

Choosing the configuration

  • Cells. Eight LiFePO₄ cells in series make 25.6 V nominal, the 24 V class.
  • Capacity. A 100 Ah pack at 25.6 V holds 2.56 kWh, above the 2.13 kWh needed.
  • Alternative. A 12 V (12.8 V) system would draw 20 A for the same power, so the cables and fuses would need to be heavier.
  • Charger. The charger or DC supply must match the 25.6 V pack.

What Eldtek confirms

  • The voltage window of the panel against the pack's range.
  • Charger and BMS communication.
  • Temperature and mounting conditions.
  • Expected life at the daily cycling pattern.

See the battery energy storage systems page for the full range.

Frequently asked questions

How many amp-hours does a 24 V, 10 A load need for 8 hours?

About 80 Ah of usable capacity, or roughly 89 Ah nominal at 90% usable depth of discharge. A 100 Ah pack covers it.

Why use 24 V rather than 12 V?

For the same power, 24 V draws half the current of 12 V, which allows thinner cables and lower losses.